What Caused Two Inverter Fires at a UK Care Home? And How to Check Your Own System
A UK care home's solar installation produced two inverter fires. When Artisan Electrics investigated, they found loose MC4 connectors and DC isolators missing from two of the three inverters. Here is what those faults are, why they matter, and what to look for on any existing system.
Video reference. Artisan Electrics, a UK solar and battery specialist firm, documented the care home call-out and their findings on their YouTube channel in September 2026. The video covers the fire damage, the connector faults, and what a correctly commissioned system should look like.
Important safety note
DC voltage from a solar array is present whenever there is daylight, even when the inverter is switched off. Working on the DC wiring, connectors, or strings always requires a qualified person. If you suspect a connector or wiring fault, do not touch it: switch the AC supply off and call a qualified solar electrician. This guide covers visual checks only.
1. What actually failed at the care home
Artisan Electrics found three distinct problems in the care home system. First, MC4 connectors on the array wiring had not been fully latched during installation. A loose MC4 creates a high-resistance join at that point, which generates heat proportional to the current flowing through it. On a system running at full output on a sunny day, that heat is enough to melt the connector housing and ignite surrounding materials.
Second, two of the three inverters had no DC isolator fitted between the string and the inverter. DC isolators are a legal requirement under BS EN 62109 and the IET Wiring Regulations. Without one, there is no safe way to de-energise the DC side of an inverter during a fault or fire.
Third, the overall cable management was poor, with cables neither labelled nor properly routed. Poor labelling slows down fault-finding significantly and increases the chance of accidental contact during any subsequent work on the system.
2. How to check MC4 connectors on your own system
Start by switching the system off at the AC isolator and the inverter before you do anything else. Then, with the system off, visually inspect the connectors you can see. Any connector showing discolouration, charring, or melted plastic is a fault that needs an electrician immediately. Any connector that you can pull apart without pressing the release clip has not been properly latched and needs to be re-seated by a qualified person.
You should not attempt to re-seat or repair MC4 connectors yourself. The connectors carry the full DC current of the string and require the correct tool to crimp and latch them safely. Incorrect re-fitting can create exactly the loose contact that caused the fires in the first place.
3. How to check for DC isolators
Each inverter should have a DC disconnect or isolator visible on or immediately next to the unit. It is typically a red or yellow rotary switch labelled "DC Isolator" or "PV Isolator". Look at every inverter in your system: if any of them does not have one, the installation has not been commissioned to the required standard.
An isolator fitted but not working is as dangerous as none. If you are unsure whether yours operates correctly, ask a qualified solar electrician to verify it rather than testing it yourself.
4. Check inverter mounting and ventilation
Inverters generate heat during operation and require clear airflow on all sides, as specified in the manufacturer data sheet. An inverter mounted flush against a wall with no gap, inside a sealed cupboard, or in a loft with poor ventilation will run hotter than designed and will degrade faster. Persistent overheating can eventually cause component failure and, in poorly installed systems, fire.
Check the clearance dimensions in your inverter's installation manual and compare them against what is actually fitted. If the clearances are not met, raise it with your installer or contact us for advice.
5. When to book an independent inspection
If your system was installed by a company that has since gone out of business, if you bought a property with solar already on the roof, or if you have any reason to doubt the quality of your installation, an independent inspection by an MCS-registered engineer is worthwhile. It gives you documented evidence of the system's condition, confirms whether the required DNO notification (G98 or G99) was actually made, and identifies any faults before they become a bigger problem.
MCS certification and what it covers
An MCS-certified installation means the work was carried out by an installer registered with the Microgeneration Certification Scheme and that the installation was notified to the DNO under G98 or G99. MCS certification is required for eligibility for the Smart Export Guarantee. It does not, by itself, guarantee that every individual connection was made correctly, but it does mean the installer was trained to the scheme's standard and can be held accountable through the MCS complaints process if something is wrong.
Frequently Asked Questions
What are MC4 connectors and why do loose ones start fires?
MC4 connectors are the standard weatherproof plug-and-socket fittings that join solar panel cables together. Each one carries the full DC current of a string of panels. A connector that is not fully latched creates a high-resistance join at that point. Resistance turns electrical energy into heat, and on a hot summer day a string running at high current can generate enough heat at a loose MC4 to melt the housing, ignite nearby cable insulation, or start a fire in the inverter it feeds.
Does every inverter need a DC isolator?
Yes. BS EN 62109 and the IET Wiring Regulations require a means of isolating the DC side of a solar inverter from the array. This allows the system to be safely de-energised for maintenance, fault-finding, or in a fire. An inverter installed without one has not been commissioned to the required standard. If you find one missing, do not operate the system until a qualified electrician rectifies it.
Is a solar fire covered by home insurance?
Most standard home insurance policies cover fire damage regardless of cause, but insurers can dispute a claim if a system was installed without the required building regulations notification (Part P in England) or without MCS certification where that is required. If your system was installed without documentation, check the position with your insurer before assuming you are covered.